Rapidox SF6 Fixed Detection System

SKU: RS6100_4 Category:

Rapidox SF6 Fixed Detection System

The Cambridge Sensotec Rapidox SF6 Fixed Detection System is a wide area monitoring solution to ensure safety for personnel working in, or who have access to, rooms that contain high voltage switchgear, circuit breakers and transformers where SF6 is at high pressure; it is important to monitor for leaks continuously.

The system comprises of either the Oldham Gas MX32 alarm measurement panel linked to one or two Oldham Gas OLCT-XPIR SF6 fixed detectors, or the larger Oldham Gas MX43 alarm measurement panel linked to between one and eight Oldham Gas OLCT-XPIR SF6 fixed detectors.

The MX32 and MX43 are compact, low-profile, wall-mount controllers that continuously monitor for SF6 leaks using remote cabled detector head units, positioned at low level around the surrounding walls. The panels include a strobe and horn to alert personnel in the event that the alarm levels for SF6 in the working environment exceed acceptable limits. Power alarm relays can be used to trigger external sirens or link into existing alarm equipment. All data can be output to a PLC or building management system.

The OLCT100-XPIR SF6 long-life infrared detector is an ATEX rated 4-20mA analogue SF6 gas transmitter designed for industrial applications in hazardous locations; the measurement range is 0-2,000ppm (the threshold limit value – or TLV, time-weighted average – for SF6 is 1,000 ppm). Each detector has programmable INSTANT, STEL and TWA alarm thresholds.

As each application is unique we offer a full installation design and installation service to meet your requirements and obligations.

Features of Rapidox SF6 Fixed Detection System

  • One to eight channel options
  • Five programmable alarms
  • STEL & TWA Alarms
  • Large graphic and multi-language LCD display
  • Easy to use menus
  • Lockable Toggle Latch (MX32)
  • LED bars assigned by zone
  • Optional SD memory card
  • Ideal for industrial applications

 

Specification Specification
Operating Temperature -20 to +50°C
Voltage 100 to 240V AC or 21 to 28V DC
Battery Backup Optional battery pack for continuous operation during power outage
Alarms Klaxon and Strobe included
Alarm Relays Programmable alarm relays per channel and 1 fault relay
(non-programmable)
Data Outputs RS485 Modbus 4 RTU (digital), analogue outputs and external relays (for alarms)
Data Storage Optional SD memory card
Measurement Time Continuous on-line
Calibration Annual on-site calibration recommended
Display Large graphical LCD back lit and multi language
Dimensions MX32 is 265 x 266 x 96 mm
MX43 is 370 x 299 x 109 mm, both in a wall-mounted IP55 case
Weight MX32 – 1.8kg
MX43 – 4kg
Detector Range 0-2,000 ppm SF6

Reviews

There are no reviews yet.

Be the first to review “Rapidox SF6 Fixed Detection System”

Your email address will not be published. Required fields are marked *